W-C-596/114C
REQUIREMENTS:
Design and configuration: See figure 1.
Dimensions: Shall conform to NEMA WD 6, configuration L7-15R. Armored construction: Not acceptable.
Ratings:
Voltage: 277 volts. Current: 15 amperes. Frequency: 50/60 hertz.
Mating connector: W-C-596/113, and W-C-596/115.
Strain relief: Accommodate cable diameter .300 - .575 inch.
Part or Identifying Number (PIN): The PIN consists of the prefix W-C, the basic specification number, the specification sheet number, and the style number.
W-C- 596 /114 -1
Style number (see table I) Specification sheet number Specification number
W-C Prefix
Supersession and cross reference: See table II.
TABLE I. Dash number.
Dash no. |
Supersedes style |
Description |
1 |
Cable outlet |
TABLE II. Supersession and cross reference. 1/
Active Government PIN |
Superseded numbers |
|||||
CAGE 39317 |
CAGE 79409 |
CAGE 74545 |
CAGE 71183 |
CAGE 04009 |
CAGE 81091 |
|
W-C-596/114-1 |
4799-C 4779-CY 47CM79-CY |
4772 4780 |
4780 |
1/ CAGE is the Commercial and Government Entity code which is assigned and maintained by
Defense Logistics Information Service (DLIS) in Battle Creek, MI.
Changes from previous issue. Marginal notations are not used in the revision to identify changes with respect to the previous issue due to the extensiveness of the changes.
Referenced documents. In addition to W-C-596, this document references the following: W-C-596/113
W-C-596/115
NEMA WD 6
2