W-C-596/13D
REQUIREMENTS:
Design and configuration: Hospital grade (see figure 1). Wiring method to provide straight-in wiring using clamp type terminals.
Dimensions: Shall conform to NEMA WD 6, configuration 5-15P. Mating face: Dead-front construction.
Armored construction: Not acceptable.
Rating:
Voltage: 125 volts. Current: 15 amperes. Frequency: 50/60 hertz.
Mating connector: W-C-596/11, W-C-596/12, or W-C-596/14.
Strain relief: Accommodate cable diameter .325 - 575 inch (8.26 - 14.60 mm). Blade strength: Connectors shall not have wires connected to terminals during test. Part or Identifying Number (PIN): W-C-596/13- (dash number from table I). Supersession and cross reference: See table II.
TABLE I. Dash number.
Dash no. |
Supersedes style |
Description |
A(max) |
B(max) |
3 1/ |
D21, D22, D23, D24, D25, D26, D27 |
Straight, dead front plug |
2.750 |
1.550 |
4 2/ |
D21, D22, D23, D24, D25, D26, D27 |
Angled, dead front plug |
---- |
---- |
5 3/ |
Straight, dead front plug |
1.90 |
1.250 |
1/ W-C-596/13-3 supercedes W-C-596/13-1.
2/ W-C-596/13-4 supercedes W-C-596/13-2.
3/ W-C-596/13-5 is a miniature version of W-C-596/13-3 for use with test equipment where power cables are stored within the equipment.
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business