W-C-596/42D
REQUIREMENTS:
Design and configuration: General grade or hospital grade (see figure1 and table I). Dimensions: Shall conform to NEMA WD 6, configuration 5-20P.
Armored construction: Not acceptable. Mating face: Dead-front construction.
Blade strength: Connectors shall not have wires connected to terminals during test.
Ratings:
Voltage: 125/250 volts. Current: 20 amperes. Frequency: 50/60 hertz.
Mating connector: W-C-596/40 or W-C-C596/41.
Strain relief: Accommodate cable diameter .325 -.655 inch (8.26-16.64 mm). Part or Identifying Number (PIN): W-C-596/42- (dash number from table I). Supersession and cross reference: See table II.
TABLE I. Dash number.
Dash no. |
Supersedes style |
Description |
1 |
X21, X23, X26 |
Straight plug, General grade |
2 |
X21, X23, X26 |
Angle plug, General grade |
3 |
Straight plug, Hospital grade |
|
4 |
Angle plug, Hospital grade |
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business