W-C-596/126C
REQUIREMENTS:
Design and configuration: See figure 1.
Dimensions: Shall conform to NEMA WD 6, configuration L15-20R. Armored construction: Not acceptable.
Ratings:
Voltage: 250 volts. Current: 20 amperes.
Frequency: 50/60 hertz, 3-phase.
Mating connector: W-C-596/125 and W-C-596/127.
Strain relief: Accommodate cable diameter .465 - .710 inch.
Part or Identifying Number (PIN): The PIN consists of the prefix W-C, the basic specification number, the specification sheet number, and the style number.
W-C- 596 /126 -1
Style number (see table I) Specification sheet number Specification number
W-C Prefix
Supersession and cross reference: See table II.
TABLE I. Dash number.
Dash no. |
Supersedes style |
Description |
1 |
Cable outlet |
TABLE II. Supersession and cross reference. 1/
Active Government PIN |
Superseded numbers |
||
CAGE 74545 |
CAGE 04009 |
CAGE 81091 |
|
W-C-596/126-1 |
2423 24CM23 |
6423 6424 |
L1520-C |
1/ CAGE is the Commercial and Government Entity code which is assigned and maintained by
Defense Logistics Information Service (DLIS) in Battle Creek, MI.
Changes from previous issue. Marginal notations are not used in the revision to identify changes with respect to the previous issue due to the extensiveness of the changes.
Referenced documents. In addition to W-C-596, this document references the following: W-C-596/125
W-C-596/127
NEMA WD 6
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.