W-C-596H/GEN
TABLE I. Qualification testing for general grade connectors.
Inspection |
Plug |
Receptacle |
Cable outlet |
Male inlet |
Requirement paragraph |
Test paragraph |
Group I (6 samples) Retention of plugs (UL 498) 1/ Gripping Terminal strength Current overload Temperature rise Retention of plugs (UL 498) 1/ Dielectric withstanding voltage Insulation resistance Isolated ground 2/ Visual and mechanical |
x x x x |
x x x x x x x x x x |
x x x x x x x x x |
x x x x |
3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.1 3.6.6 3.6.7 3.6.8 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.2 4.6.7 4.6.8 4.6.9 4.6.1 |
Group II (6 samples) Heat resistance (85°C, 2 hours) Mechanical shock Dielectric withstanding voltage Insulation resistance Crushing (75 pounds) Strain relief (general grade) Visual and mechanical |
x x x x x x x |
x x x x |
x x x x x x x |
x x x x |
3.6.9 3.6.10 3.6.6 3.6.7 3.6.11 3.6.12 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.10 4.6.11 4.6.7 4.6.8 4.6.12 4.6.13 4.6.1 |
Group III (6 samples) Assembly security 3/ Integrity of assembly (UL 498) 1/ Potential drop in grounding connections (UL 498) 1/ Receptacle grounding contact (UL 498) 1/ Visual and mechanical |
x x |
x x x |
x x x |
x x |
3.6.13 3.6.14a 3.6.14b 3.6.14c 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.14 4.6.15a 4.6.15b 4.6.15c 4.6.1 |
Group IV (6 samples) Blade strength Accelerated aging (UL 498) 1/ 4/ Visual and mechanical |
x x x |
x x |
x x |
x x |
3.6.15 3.6.14d 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.16 4.6.15d 4.6.1 |
1/ Not required if UL or CSA listed.
2/ Isolated ground receptacle only.
3/ For 15 and 20 ampere, 125 volt duplex, nonlocking receptacles only.
4/ Rubber and PVC materials only.
9
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business