W-C-596H/GEN
TABLE II. Qualification testing for hospital grade connectors.
Inspection |
Plug |
Receptacle |
Cable outlet |
Male inlet |
Requirement paragraph |
Test paragraph |
Group I (6 samples) Retention of plugs (UL 498) 1/ Gripping Terminal strength Current overload Temperature rise Retention of plugs (UL 498) 1/ Dielectric withstanding voltage Insulation resistance Isolated ground 2/ Visual and mechanical |
x x x x |
x x x x x x x x x x |
x x x x x x x x x |
3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.1 3.6.6 3.6.7 3.6.8 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.2 4.6.7 4.6.8 4.6.9 4.6.1 |
|
Group II (6 samples) Heat resistance (85°C, 2 hours) Mechanical shock Dielectric withstanding voltage Insulation resistance Crushing 1/ Strain relief 1/ Visual and mechanical |
x x x x x x x |
x x x x |
x x x x x x x |
3.6.9 3.6.10 3.6.6 3.6.7 3.6.11 3.6.12 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.10 4.6.11 4.6.7 4.6.8 4.6.12 4.6.13 4.6.1 |
|
Group III (6 samples) Assembly security 3/ Receptacle grounding contact (UL 498) 1/ 4/ Mold stress relief (UL 498) 1/ Salt spray (corrosion) (when specified) Visual and mechanical |
x x |
x x x x x |
x x |
3.6.13 3.6.14c 3.6.14f 3.6.16 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.14 4.6.15c 4.6.15f 4.6.17 4.6.1 |
|
Group IV (6 samples) Temperature rise Blade strength Impact test (UL 498) 1/ Accelerated aging (UL 498) 1/ 5/ Visual and mechanical |
x x x x |
x x x x |
x x x x |
3.6.5 3.6.15 3.6.17 3.6.14d 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.6 4.6.16 4.6.18 4.6.15d 4.6.1 |
|
Group V (6 samples) Crushing (UL 498, hospital grade) (500 pounds) Visual and mechanical |
x x |
x x |
3.6.11 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.12 4.6.1 |
||
Group VI (8 samples) 1/ Conditioning (UL 498) (with plug) Grounding pin retention (method I) (UL 498) Abrupt removal (UL 498) Grounding pin retention (method I) (UL 498) Line blade retention (UL 498) Grounding contact temperature (UL 498) Ground contact resistance (UL 498) Fault current test (UL 498) Visual and mechanical |
x x x x x x x x x |
3.6.14g 3.6.14e 3.6.14h 3.6.14e 3.6.14i 3.6.14j 3.6.14k 3.6.14l 3.1, 3.4, 3.5, 3.7 and 3.8 |
4.6.15g 4.6.15e 4.6.15h 4.6.15e 4.6.15i 4.6.15j 4.6.15k 4.6.15l 4.6.1 |
See footnotes at end of table.
10
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business